Page 4 of 6 <br /> Combination Tank Component Cross Section <br /> Approved Manhole Covers With Warning Labels <br /> and Locking Device/4"Min Above Final Grade <br /> \ Weather Proof Junction Box <br /> Electric per NEC 300&COMM. <br /> >orr=to 12"" <br /> 4" 16.28 WAC <br /> = 1 <br /> Above Final Grade y <br /> Disco <br /> Alternate Outlet Location <br /> W/Approved 4"Sleeve <br /> Inlet Approved Force Main Diam.= 2 " <br /> Effluent Filter <br /> Baffl� <or=to 1/8" Weep Hole or Anti Siphon Device <br /> Particle Size A <br /> W1000/600-MR <br /> B Pump Off Elev. 85.81' <br /> Wieser C <br /> Tank Mfr. Concrete <br /> D 84 81' <br /> Dose Tank Elev. <br /> Vertical Difference Between Pump Off and Distribution Pipe= 5.49' <br /> Minimum Required Supply Pressure......................................= NA <br /> 40 FT.of ForceMain x 2.58 Friction Factor/10017T. ...= 1.03 <br /> Total Dynamic Head....................= 6.52' <br /> Number of Doses...= 5 Per Day Gal.Per Day/#of Doses= 60 Gal. <br /> Volume of Backflow....................................................................= 6.52 Gal. <br /> Total Dose Volume..................................................................... = 66.52 Gal. <br /> Pump Tank Capacity 602.82 Gallons Dimensions Inches Gallons <br /> Pump Tank Volune 11_82 Gal/Inch A 30.48 360.27 <br /> Zoeller B 2 23_64 <br /> Pump Mfr. C 6_52 77_07 <br /> Pump Model Model 53/57 D 12 141.84 <br /> Minimum Discharge Rate= NA GPM <br /> Alarm Mfr. S.J.Electro Total= 51 602.82 <br /> Alarm Model 101-01H <br /> Bed Tank per COMM.83.45(5) <br /> Anchor Tank as necessary to negate buoyant forces per COMM.83.43(8)(g). <br /> Note: Pump Controls and Alarm Switch require seperate circuits. <br /> R®INIM <br />