Pg.4 of 7 <br /> DoseTank Component Cross Section <br /> Approved Manhole Covers With Warning Labels <br /> and Loclong Device/4"Min.Above Final Grade <br /> Weather Proof Junction Box <br /> Electric per NEC 300&COMM. <br /> 4" Sch.40 Vent 16.28 WAC <br /> >or=to 12" <br /> Above Final Grade <br /> Disco <br /> Alternate Outlet Location <br /> W/Approved 4" Sleeve <br /> Inlet Force Main Diam.= 2 <br /> Weep Hole or Ami Siphon Device <br /> A <br /> Note: Pump switch and alarm to be B Pump Off Elev. 77_00' <br /> wired to sepetate circuits. C <br /> Tank Mfr. Huffcutt Concrete 1000 Gal D <br /> Dose Tank Elev. 76.00' <br /> Vertical Difference Between Pump Off and Distribution Pipe= 14_25' — <br /> Minimum Required Supply Pressure......................................= NA <br /> 90' FT.of Force Main x 2.58 Friction Factor/100FT. ...= 2.32' <br /> Total Dynamic Head....................= 16_57' <br /> Number of Doses...= 7 Per Day Gal.Per Day/#of Doses=107.33 GaL <br /> Volume of Baclrilow....................................................................= 14.67 Gal. <br /> Total Dose Volume..................................................................... = 122.00 Gal. <br /> Pump Tank Capacity 1036 Gallons Dimensions Inches Gallons <br /> Pump Tank Volume 28 Gal/loch A 18.64 521.92 <br /> B 2 56 <br /> Pump Mfr. Zoeller C 4.36 122.08 <br /> Pump Model 98 D 12 336 <br /> Minimum Discharge Rate= NA GPM <br /> Approx.40 gpm Total= 37 1036 <br /> Alarm Mfr. S.J.Electro <br /> Alarm Model 101-01H <br /> Bed Tank per COMM.83.45(5) <br /> Anchor Tank as necessary to negate buoyant forces per COMM.83.43(8xg). <br />